Lighting a loading dock without shadowed areas
On a loading dock, moving from a brightly lit interior to a dark manoeuvring area creates a few seconds of blindness, exactly where forklifts and pedestrians circulate. Here is how to deal with the three areas of the dock, choose the protection and control switch-on from the opening of the doors.
5 min read

At six in the morning, a forklift driver leaves a lit warehouse and drives onto a dock that is still dark. The truck is docked, the trailer open, the ground wet. Between the inside and the manoeuvring area, the eye takes several seconds to adapt, and it is those seconds that count.
The three areas to deal with: inside, threshold, manoeuvring area
A dock is not a uniform space. The inside of the building falls under the lighting of indoor workplaces, the manoeuvring area falls under the lighting of outdoor workplaces, and the threshold belongs to both. Dealing with the three separately leads to breaks in level at the doors.
- The inside area: forklift traffic, pallet drop-off, checking documents and parcels.
- The threshold: dock leveller, seal, bumpers, wheel passage, possible step.
- The outdoor manoeuvring area: reversing the vehicle, chocking, docking, drivers moving around on foot.
The French Labour Code sets a minimum of 40 lux for outdoor areas where permanent work is carried out, and 10 lux for outdoor traffic areas and routes. A docking area clearly falls into the first case.
Contrast between inside and outside and the adaptation of the eye
The eye adapts slowly when it moves from a high level to a low level. An abrupt difference between an indoor preparation area and a poorly lit outside creates temporary visual discomfort, exactly where vehicles and pedestrians cross.
The countermeasure is to create a transition rather than a threshold. In practice, the level of the outdoor area immediately in front of the doors is raised, then allowed to decrease towards the edges. The same logic applies during the day, in reverse, when a forklift driver comes in from a very bright yard.
This transition is checked on the ground by walking slowly in both directions, at the least favourable time. A survey carried out in the middle of the day shows nothing of the problem.
Lighting the inside of the trailer
A docked trailer is an enclosed volume that the general lighting never reaches. The light from the building stops at the tailgate and the back of the body stays dark over its whole depth, especially for manual unloading.
There are two solutions. The articulated dock light arm, moved by the operator, follows the progress of unloading right to the back. The fixed luminaire above the door, placed above the dock leveller, lights the first third of the trailer and serves as a permanent supplement. The arm remains the only satisfactory answer for complete manual unloading.
This equipment is exposed to impacts from pallets and to the movements of the trailer. A robust body, protected wiring and a properly designed joint matter more than the flux stated on the data sheet.
Forklift traffic and pedestrian visibility
On a dock, the main risk is a collision between a vehicle and a person. A pedestrian's visibility depends on their contrast with the background, and therefore on the vertical illuminance on their silhouette, not on the illuminance at floor level.
Grazing light from one side only creates black silhouettes against the light. Distributed lighting, with crossed contributions, reveals people whatever their direction of travel. Pedestrian routes marked on the ground lose all their value if they cannot be read at night.
Outdoor LED floodlights mounted on the façade above the doors cover the manoeuvring area, provided they are aimed downwards and not at the approaching driver, who is reversing using the mirrors.
Exposure to the weather and choice of ingress protection rating
The dock combines driving rain, spray from wheels, frost and temperature differences between the heated inside and the outside. The ingress protection rating is read in two digits: the first concerns solid bodies and dust, the second water.
| Location | Dominant exposure | Expected level of protection |
| --- | --- | --- |
| Inside the building, set back from the threshold | dust, handling impacts | protection against dust and a resistant body |
| Above the door and immediate surroundings of the threshold | spray, damp, draughts | protection against water jets from all directions |
| Façade and outdoor manoeuvring area | rain, frost, washing of the yard | enhanced protection against water and dust |
The ingress protection rating says nothing about the ageing of seals or the long-term durability of materials. It serves as a first filter, supplemented by the nature of the body, the quality of the cable glands and the operating temperature range stated by the manufacturer.
Impacts on low-mounted luminaires and mechanical protection
Anything installed less than three metres high on a dock eventually gets hit: forklift forks, the corner of a pallet, a moving tailgate. The IK rating characterises the resistance of the luminaire to mechanical impacts and is read in the same way as the ingress protection rating.
Two precautions complete the choice of product. The first is to move the luminaire out of the path of vehicles, even if it means placing it higher with a suitable beam. The second is to protect low points with a guard or a cover, checking that this protection does not trap dirt.
Waterproof linear battens surface-mounted along the inside wall, out of the traffic area, last longer than a luminaire suspended in the middle of the passage.
Automatic control linked to the opening of the doors
The outdoor lighting of a dock has no reason to operate continuously. Triggering on door opening, on vehicle presence or on motion detection covers the real needs of operations.
The tricky point is the run-up time. A forklift driver must not wait for the light to come up before starting the manoeuvre. A permanent standby level, supplemented by a switch to full output when triggered, removes this wait and limits sudden loads on the equipment.
A photometric simulation of the dock and its manoeuvring area makes it possible to check the continuity of levels between the inside, the threshold and the outside before fixing the layouts and mounting heights.
Retrace the complete route of a forklift driver at night, from the preparation area to the back of the trailer, and note each point where the eye loses its bearings.
Then select the suitable luminaires in the storage and logistics category.
Further reading: Car park lighting: height, layout and uniformity and Office lighting: LED panel or linear pendant. Reference: NF EN 12464-2 standard on outdoor workplace lighting (AFNOR).
In the Rexylum catalogue: REXPACK-300 · High-Performance Wall Pack and REXBATTEN U-LOCK · Adjustable-Power LED Monobloc.